Powered by GoogleTranslate

Accident Report Detail

Accident Summary Nr: 201798865 - Electric Shock - Direct Contact with Energized Conductor

Accident Summary Nr: 201798865 -- Report ID: 0950644 -- Event Date: 06/10/2004
Inspection NrDate OpenedSICNAICSEstablishment Name
30133232606/16/20044911221122So. California Edison

Abstract: Three meter technicians were installing transformers in new metering switchgear at a cogeneration facility at a college campus. After opening the disconnect on the metering compartments, one of the workers cut the insulation boards at the lower portion of the metering compartment. This operation generated dust, and the worker used a rag to wipe off the boards. As he was wiping the top of the metering compartment, the worker contacted an energized 12-kilovolt conductor. He received an electric shock and sustained burns to his hands. He was hospitalized for his injuries. The door at the upper portion of the metering compartment had not been closed while the employees were working on the switchgear, and the employees had not been using personal protective equipment.

Keywords: BURN, ELEC PROTECT EQUIP, ELECTRICAL, CLEANING, ELECTRICIAN, LOCKOUT, UNGUARDED LIVE PARTS, E PTD, ELEC UTILITY WORK, ELECTRIC SHOCK

Employee Details
Employee # Inspection Nr Age Sex Degree of Injury Nature of Injury Occupation
1 301332326 Hospitalized injury Burn/Scald(Heat) Power plant operators

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close