Accident Summary Nr: 201153764 - Employees Asphyxiated While Working in Manhole

Accident Summary Nr: 201153764 -- Report ID: 0950633 -- Event Date: 05/22/2000
Inspection NrDate OpenedSICNAICSEstablishment Name
11994752105/22/200017310Cadri Company, Inc

Abstract: Two employees of an electrical contractor were working in a 7.9-meter-deep sump manhole at a water desalination facility site under construction. An employee of a general contractor found the employees unconscious at the bottom of the manhole. An outside rescue service from a local fire department responded and found the atmosphere in the manhole to contain 8 percent oxygen at the bottom of the sump. The two employees died of hypoxic asphyxia. Postaccident evaluations found oxygen levels as low as 2 percent and elevated levels of nitrogen and carbon dioxide. The sump was found to be in contact with warm, moist soil through a series of interconnected perforated pipes designed to drain excess groundwater. It was suspected that biological activity in the surrounding soil consumed the available oxygen and generated excess levels of nitrogen and carbon dioxide.

Keywords: OXYGEN DEFICIENCY, UNCONSCIOUSNESS, ASPHYXIATED, CONFINED SPACE, MANHOLE
Accident Details
End Use Project Type Project Cost Stories Non-building Height Fatality
Sewer/water treatment plant New project or new addition $5,000,000 to $20,000,000 26 X

Employee Details
Employee # Inspection Nr Age Sex Degree of Injury Nature of Injury Occupation Construction
1 119947521 Fatality Asphyxia Supervisors; electricians & power transm. install. Distance of Fall: feet
Worker Height Above Ground/Floor: feet
Cause: Installing underground plumbing conduit
Fatality Cause: Asphyxiation/inhalation of toxic vapor
2 119947521 Fatality Asphyxia Electricians Distance of Fall: feet
Worker Height Above Ground/Floor: feet
Cause: Installing underground plumbing conduit
Fatality Cause: Asphyxiation/inhalation of toxic vapor

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.