Powered by GoogleTranslate

Accident Report Detail

Accident Summary Nr: 201120086 - ELECTRIC SHOCK - DIRECT CONTACT WITH ENERGIZED PARTS

Accident Summary Nr: 201120086 -- Report ID: 0950613 -- Event Date: 01/27/1997
Inspection NrDate OpenedSICNAICSEstablishment Name
11974597402/11/199749310Pacific Gas And Electric Company

Abstract: A power line worker and his supervisor had pumped water from an underground electrical vault. The power line worker entered the vault and attached a rope to the switch handle of a 15-kilovolt, 400-ampere T-GRAM oil switch, which controlled a transformer in the same vault. He had attached the rope so that he could operate the handle from outside the vault. The switch handle had three positions: on, off, and test; and the employee was going to use the rope to pull the handle from the on position to the off position. Unfortunately, when he pulled the rope, the handle went past the off position to the test position. A metal block used to prevent this from happening was not in place. The supervisor and the power line worker assumed that the handle was in the off position even though a brief inspection would have revealed it was not. (The switch was visible to both from outside the vault.) When the power line worker reentered the vault to remove the rope, he contacted an unguarded, energized bushing on the oil switch and received an electric shock. He was hospitalized with serious injuries.

Keywords: ELECTRICAL, ELECTRIC SWITCH, POWER LINE WORKER, LOCKOUT, E PTD, UNDRGRD INSTALLATION, ELEC UTILITY WORK, ELECTRIC SHOCK, INATTENTION

Employee Details
Employee # Inspection Nr Age Sex Degree of Injury Nature of Injury Occupation
1 119745974 Hospitalized injury Electric Shock Misc. electrical & electronic equipment repairers

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.