Accident Summary Nr: 201097177 - Utility Worker Was Electrocuted Changing Dampers

Accident Summary Nr: 201097177 -- Report ID: 0950645 -- Event Date: 01/13/2004
Inspection NrDate OpenedSICNAICSEstablishment Name
12611070901/13/20044911221111Pg & E

Abstract: A power line worker was replacing dampers on a metal tower supporting a two-circuit, 115-kilovolt overhead power line. The line on which he was replacing the dampers was deenergized, but the parallel circuit was not. The crew had changed dampers on several towers. This was the first tower for the power line worker to change dampers on this day. Without waiting for the grounding equipment to be raised, the employee started to work on the dampers. He was electrocuted when he contacted one of the power line conductors. The parallel energized line had induced voltage on the deenergized line. The employee had performed this task many times before and was trained for the work.

Keywords: ELEC PROTECT EQUIP, OVERHEAD POWER LINE, PROTECTIVE GROUNDING, ELECTRICAL, POWER LINE WORKER, ELECTROCUTED, E PTD, INDUCED CURRENT, ELEC UTILITY WORK

Employee Details
Employee # Inspection Nr Age Sex Degree of Injury Nature of Injury Occupation
1 126110709 Fatality Electric Shock Electrical power installers and repairers

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close