Accident Summary Nr: 200783843 - Employee electrocuted in contact with bare conductors

Accident Summary Nr: 200783843 -- Report ID: 0626300 -- Event Date: 07/01/2006
Inspection NrDate OpenedSICNAICSEstablishment Name
30953902107/03/20061731238210Globe Electric Service

Abstract: On July 1, 2006, Employee #1, of Globe Electric Service, was in the attic of an existing home, working on an energized multi-conductor branch circuit to repair a malfunctioning 120-volt receptacle in the kitchen. The 20-amp branch circuit originated from a single panelboard in the master bedroom walk-in closet. In Employee #1's immediate work area was a blue PVC single gang nail-on box that did not have a cover. Three 12/2 type NM-B cables--a cable from a service panel, a cable to an electrical outlet, and a cable to a ceiling fan in the kitchen--entered the box and were spliced together. None of the splices were made with wire nuts and the bare conductors were exposed. The Type NM-B cable to the ceiling fan was pulled from the box, and the bare conductors for it were also exposed. As he was working, Employee #1 apparently contacted one or more bare conductors and was electrocuted. He had not been protected from contacting the energized equipment, parts, or circuits by guarding, isolation, or insulation. Employee #1 was not wearing, nor had he been provided, voltage-rated rubber gloves. No safety-related work practices had been developed and implemented for the work he was doing.

Keywords: ELEC PROTECT EQUIP, REPAIR, ELECTRICAL, WORK RULES, ELECTROCUTED, STRUCK AGAINST, CONSTRUCTION, ELEC CIRC PART--MISC, ELECTRICAL SPLICE, UNTRAINED
Accident Details
End Use Project Type Project Cost Stories Non-building Height Fatality
Single family or duplex dwelling Maintenance or repair Under $50,000 1 X

Employee Details
Employee # Inspection Nr Age Sex Degree of Injury Nature of Injury Occupation Construction
1 309539021 Fatality Electric Shock Electricians Distance of Fall: feet
Worker Height Above Ground/Floor: feet
Cause: Installing plumbing, lighting fixtures
Fatality Cause: Electrocution by touching exposed wire/source

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.