Accident Summary Nr: 170847669 - BURN - ELECTRIC METER FAILED

Accident Summary Nr: 170847669 -- Report ID: 0950651 -- Event Date: 05/11/1999
Inspection NrDate OpenedSICNAICSEstablishment Name
11994715805/12/199910410Viceroy Gold Corporation

Abstract: A crew of employees a remote gold mine was digging with a backhoe when they cut a 4160-volt underground power line. A journeyman electrician was assigned to troubleshoot the problem, and restore power to the high-voltage equipment. The 58-year-old electrician had a wealth of experience, including 20 years of high-voltage experience. After resetting the circuit breakers protecting the circuit, the electrician got a 1000-volt Fluke meter. He had assumed that the broken line was a 480-volt line. He entered the excavation without wearing rubber insulating gloves and checked the circuit with the meter. (The employer had high-voltage testing equipment and rubber insulating gloves available.) The meter failed, and the ensuing electric arc burned the employee. He was hospitalized with second- and third-degree burns on his face and hands.

Keywords: BURN, E GI V, ELECTRIC ARC, REPAIR, ELECTRICAL, PPE, ELECTRICIAN, ELECTRICAL WORK, ELECTRIC METER, ELECTRICAL FAULT

Employee Details
Employee # Inspection Nr Age Sex Degree of Injury Nature of Injury Occupation
1 119947158 Hospitalized injury Burn(Chemical) Electricians

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close