Abstract: A JOURNEYMAN POWER LINE WORKER WAS WORKING ON A BULL TENSION CABLE TRAILER. HIS ASSIGNMENT WAS TO ADJUST THE TENSION ON THE CABLE AS IT WAS BEING STRUNG ON A SET OF 40-FOOT-TALL UTILITY POLES SUPPORTING A 12-KILOVOLT OVERHEAD POWER LINE. AS THE PULL CROSSED THE SECOND POLE, THE STEEL PULLING SOCK SNAGGED ONE OF THE CONDUCTORS ON THE 12-KILOVOLT SYSTEM. THE GROUND ROD AT THE PULLING EQUIPMENT WAS BLOWN OUT OF THE GROUND, AND THE CONDUCTOR BURNED IN HALF. THE MAIN BREAKER, WHICH WAS LOCATED 5 MILES AWAY, NEVER OPENED. THE POWER LINE WORKER WAS ELECTROCUTED. (ANOTHER POWER LINE WORKER DEENERGIZED THE PULLING EQUIPMENT BY CUTTING THE PHASE CONDUCTOR AFTER DEAD-ENDING IT.)

Keywords: OVERHEAD POWER LINE, PROTECTIVE GROUNDING, ELECTRICAL, POWER LINE WORKER, ELECTROCUTED, E PTD, ELEC UTILITY WORK, TRAILER

Employee Details
Employee # Inspection Nr Age Sex Degree of Injury Nature of Injury Occupation
1 119965598 Fatality Electric Shock Electrical power installers and repairers

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close