Accident Summary Nr: 170188148 - BURN - ELECTRICAL FAULT IN SWITCH

Accident Summary Nr: 170188148 -- Report ID: 0950634 -- Event Date: 10/01/1991
Inspection NrDate OpenedSICNAICSEstablishment Name
11206824211/19/199135990Wilcox Machine

Abstract: AN EMPLOYEE CLOSED A SWITCH TO RUN A POSITIONER FOR WELDING OPERATIONS. THE SWITCH CONTROLLED ELECTRIC POWER TO A NEARBY RECEPTACLE OUTLET USED TO CONNECT A WELDER OR THE POSITIONER. AS THE EMPLOYEE WAS OPERATING ITS HANDLE, IT BROKE OFF AS SOON AS THE SWITCH WAS PARTIALLY CLOSED. AFTER HE DID THIS, THE POSITIONER WAS WORKING; HOWEVER, THE EMPLOYEE RETURNED TO THE FRONT OF THE SWITCH TO SEE WHY THE HANDLE BROKE. APPARENTLY, THE COVER ON THE SWITCH, WHICH WAS A TYPE THAT HAS SLIDING CONTACTS, WAS NOT PROPERLY SNAPPED INTO PLACE; AND, SINCE THE TURNING MECHANISM WOULD BE OUT OF ALIGNMENT, THE SWITCH WOULD NOT CLOSE FULLY. IN THE MEANTIME, THE COVER OF THE SWITCH SLID DOWN AND CONTACTED THE HALF-CLOSED BLADES ON THE THREE POLES OF THE SWITCH (THE THREE POINTS OF CONTACT WERE QUITE EVIDENT ON THE SWITCH COVER). THE METAL COVER'S CONTACTING THE ENERGIZED PARTS OF THE SWITCH CAUSED AN ELECTRICAL FAULT. THE ENSUING ELECTRIC ARC BURNED THE EMPLOYEE, WHO WAS STANDING IN FRONT OF THE SWITCH. THE EMPLOYEE WAS HOSPITALIZED FOR HIS INJURY. THE CAUSE OF THE LOOSENESS OF THE COVER COULD NOT BE DETERMINED.

Keywords: BURN, E GI V, ELECTRIC ARC, ELECTRICAL, ELECTRIC SWITCH, ELECTRICAL FAULT

Employee Details
Employee # Inspection Nr Age Sex Degree of Injury Nature of Injury Occupation
1 112068242 Hospitalized injury Burn/Scald(Heat) Welders and cutters

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close