Powered by GoogleTranslate

Accident Report Detail

Accident Summary Nr: 170176572 - ELECTRIC SHOCK - DIRECT CONTACT WITH ENERGIZED PARTS

Accident Summary Nr: 170176572 -- Report ID: 0950611 -- Event Date: 05/23/1991
Inspection NrDate OpenedSICNAICSEstablishment Name
11173800106/12/199136460Boyd Lighting Fixture Co.

Abstract: An employee was repairing a testing instrument. He contacted energized parts and received an electric shock. The electric shock caused him to break his left arm and dislocate his shoulder. He was hospitalized for his injuries.

Keywords: E GI II, ELEC PROTECT EQUIP, FRACTURE, REPAIR, ELECTRICAL, TEST EQUIPMENT, DISLOCATED, ELEC CIRC PART--MISC, ELECTRIC SHOCK, ARM

Employee Details
Employee # Inspection Nr Age Sex Degree of Injury Nature of Injury Occupation
1 111738001 Hospitalized injury Electric Shock Not specified mechanics and repairers

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close