Powered by GoogleTranslate

Accident Report Detail

Accident Summary Nr: 170005995 - BURN - ELECTRICAL FAULT IN VOLTMETER

Accident Summary Nr: 170005995 -- Report ID: 1055360 -- Event Date: 09/04/1993
Inspection NrDate OpenedSICNAICSEstablishment Name
11543027409/08/199317310Cascade Electric Services Inc

Abstract: An employee was tracing a secondary circuit that had a fault. He had checked a secondary junction box and found a failed elbow. He then moved to a three-phase, pad-mounted transformer. He discovered an open fuse on the 7200-volt primary side of the transformer. He decided to test the fuse with a low-voltage voltmeter. The voltmeter failed, and the employee sustained burns on his hands, face, and right arm from the ensuing electric arc. The employee, who was not qualified to work on the high voltage side of the transformer, was hospitalized for his injuries.

Keywords: BURN, ELECTRIC ARC, ELECTRICAL, ELECTRICIAN, TEST EQUIPMENT, E PTD, ELEC UTILITY WORK, ELECTRICAL FAULT, TRANSFORMER, UNTRAINED

Employee Details
Employee # Inspection Nr Age Sex Degree of Injury Nature of Injury Occupation
1 115430274 Hospitalized injury Electric Shock Electricians

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close