Powered by GoogleTranslate

Accident Report Detail

Accident Summary Nr: 14530133 - ELECTRIC SHOCK - DIRECT CONTACT WITH ENERGIZED PARTS

Accident Summary Nr: 14530133 -- Report ID: 0111700 -- Event Date: 05/31/1989
Inspection NrDate OpenedSICNAICSEstablishment Name
10085863806/01/198917310Lincoln Electrical Contracting Corp.

Abstract: TWO ELECTRICIANS AND THEIR FOREMAN WERE TROUBLESHOOTING A 277-VOLT EMERGENCY LIGHTING CIRCUIT. THE TWO ELECTRICIANS WERE DISCONNECTING THE FAULTY CIRCUIT AT TWO JUNCTION BOXES LOCATED ABOVE A CEILING. THEY HAD ASSUMED THAT THE CIRCUIT BREAKER FOR THE CIRCUIT WAS OFF. ONE OF THE ELECTRICIANS HAD TESTED FOR POWER AT ONE OF THE JUNCTION BOXES AND FOUND THE CIRCUIT TO BE DEENERGIZED. THE FOREMAN WAS IN THE ELECTRICAL ROOM TROUBLESHOOTING THE SAME CIRCUIT AND WAS TURNING THE CIRCUIT BREAKER OFF AND ON. THE ELECTRICIAN WHO HAD TESTED THE CIRCUIT RECEIVED AN ELECTRIC SHOCK (HE WAS NOT LIST AS BEING INJURED) AND, MOMENTS LATER, HEARD THE OTHER ELECTRICIAN YELL. A THIRD ELECTRICIAN WENT INTO THE CEILING AFTER HEARING THE SAME YELL AND FOUND THE SECOND ELECTRICIAN LYING ON THE JUNCTION BOX, CONVULSING. THE CIRCUIT WAS DEENERGIZED AND CARDIO-PULMONARY RESUSCITATION WAS BEGUN IN THE CEILING AREA. IN SPITE OF THESE RESCUE EFFORTS, THE EMPLOYEE DIED.

Keywords: LIGHTING CIRCUIT, E GI IV, ELECTRICAL, ELECTRICIAN, ELECTROCUTED, ELECTRICAL WORK, LOCKOUT, ELECTRIC CONDUCTOR, ELECTRIC SHOCK, ELECTRICAL BOX

Employee Details
Employee # Inspection Nr Age Sex Degree of Injury Nature of Injury Occupation
1 100858638 Fatality Electric Shock Electricians

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close