Powered by GoogleTranslate

Accident Report Detail

Accident Summary Nr: 14496673 - ELECTRIC SHOCK - GROUND FAULT IN ELECTRICAL BOX

Accident Summary Nr: 14496673 -- Report ID: 0627100 -- Event Date: 10/20/1987
Inspection NrDate OpenedSICNAICSEstablishment Name
10238807110/20/198734440Triangle Engineering Of Arkansas, Inc.

Abstract: As an employee of an engineering firm was reaching for a metal basket, he touched a punch press with his shoulder and was electrocuted. A safety inspection determined that, because of an electrical fault, current was flowing between the 31.8-metric-ton punch press and the metal basket, which was touching a 54.4-metric-ton punch press. Further investigation revealed that the cause of the fault was a bare connection inside a motor terminal box on a hydraulic bender located adjacent to the smaller press. A wire nut had come off a connection, and the twisted conductor ends were in contact with the motor housing. The smaller press and hydraulic bender apparently were not properly grounded.

Keywords: ELEC INSULATION, ELECTRICAL, E GI VII, ELECTROCUTED, BENDING MACHINE, GROUND FAULT, EQUIPMENT GROUNDING, ELECTRICAL BOX, PUNCH PRESS, ELEC EQUIPMENT--MISC

Employee Details
Employee # Inspection Nr Age Sex Degree of Injury Nature of Injury Occupation
1 102388071 Fatality Electric Shock Occupation not reported

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close