Accident Summary Nr: 14424360 - ELECTRIC SHOCK - GROUND FAULT IN FLEXIBLE CONDUIT

Accident Summary Nr: 14424360 -- Report ID: 0729300 -- Event Date: 08/11/1986
Inspection NrDate OpenedSICNAICSEstablishment Name
10312524108/14/198676230Schneider Service Co.

Abstract: AN EMPLOYEE HAD INSTALLED A NEW PUMP MOTOR ON A HOLDING TANK FOR A COMMERCIAL HOT WATER TANK. THE WIRING FOR THE PUMP HAD NOT YET BEEN CONNECTED TO ITS 120-VOLT SUPPLY. THE FLOOR WHERE THE EMPLOYEE WAS WORKING WAS WET FROM THE CHANGE OF PUMPS IN THE CLOSE QUARTERS BETWEEN THE TANKS. THE SUPPLY CIRCUIT FOR THE PUMP WAS STILL ENERGIZED TO ENABLE THE CONTROLS TO BE CHECKED BEFORE THE MOTOR WAS CONNECTED. ONE OF THE ENERGIZED CONDUCTORS, WHICH WAS CONTAINED WITHIN A FLEXIBLE CONDUIT, HAD ITS INSULATION SKINNED. THE EXPOSED PORTION OF THE CONDUCTOR WAS CONTACTING THE CONDUIT WALL, CAUSING A GROUND FAULT. WHEN THE EMPLOYEE CONTACTED THE CONDUIT, HE WAS ELECTROCUTED.

Keywords: ELEC INSULATION, ELECTRICAL, E GI VII, ELECTROCUTED, ELECTRICAL WORK, GROUND FAULT, ELECTRIC CONDUCTOR

Employee Details
Employee # Inspection Nr Age Sex Degree of Injury Nature of Injury Occupation
1 103125241 Fatality Electric Shock Occupation not reported

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close