Accident Report Detail

Accident Summary Nr: 14412498 - ELECTRIC SHOCK - CONTACT WITH OVERHEAD LINE THRU POLE GROUND

Accident Summary Nr: 14412498 -- Report ID: 0626600 -- Event Date: 05/21/1987
Inspection NrDate OpenedSICNAICSEstablishment Name
10073918405/22/198716230L.W.K. Electrical Co., Inc.

Abstract: A power line crew was setting utility poles. The crew was using an electric line truck with a boom to hoist a replacement pole next to an existing pole. The employees were setting the new pole between two phase conductors of a three-phase, 7200-volt-to-ground overhead power line. The employees had put rubber insulating line hose on the middle phase conductor and had installed a No. 4 solid copper ground wire on the pole. As the line truck was positioning the pole between the phase conductors, the ground wire on the pole contacted an uninsulated portion of the overhead line. One of the employees on the crew was apparently getting a drink of water by the truck. The employee, who had one hand on the truck when the contact occurred, was electrocuted.

Keywords: BOOM TRUCK, OVERHEAD POWER LINE, ELECTRICAL, POWER LINE WORKER, ELECTROCUTED, E PTD, ELEC UTILITY WORK, ELECTRIC CONDUCTOR, UTILITY POLE

Employee Details
Employee # Inspection Nr Age Sex Degree of Injury Nature of Injury Occupation
1 100739184 Fatality Electric Shock Electrical power installers and repairers

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close