Accident Summary Nr: 14392997 - ELECTRIC SHOCK - CONTACT WITH ENERGIZED PARTS

Accident Summary Nr: 14392997 -- Report ID: 0625700 -- Event Date: 04/20/1985
Inspection NrDate OpenedSICNAICSEstablishment Name
192196404/24/198528130Liquid Air Corporation

Abstract: Two employees were replacing a fuse in a 4160-volt starter (switchgear) for an air compressor. The switchgear was supplied with an interlock requiring a lever to be pulled down to disengage the contactor unit from the bus. The interlock was designed to prevent the cabinet door from opening when the contactor unit is engaged. It was also designed to prevent the cart to be racked in when the cabinet door is open. The interlock was broken, and one of the employees was pushing on the cart while the other employee was jiggling the lever to align the cart so it could be racked in. The cart contacted the 4160-volt bus, electrocuting the employee pushing on it.

Keywords: E GI V, ELECTRICAL, ELECTRICIAN, ELECTROCUTED, ELECTRICAL WORK, INTERLOCK, LOCKOUT, SWITCHGEAR, MECH MALFUNCTION

Employee Details
Employee # Inspection Nr Age Sex Degree of Injury Nature of Injury Occupation
1 1921964 Fatality Electric Shock Electricians

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close