Powered by GoogleTranslate

Accident Report Detail

Accident Summary Nr: 14383525 - ELECTRIC SHOCK - GROUND FAULT IN RECTIFIER

Accident Summary Nr: 14383525 -- Report ID: 0524530 -- Event Date: 05/26/1993
Inspection NrDate OpenedSICNAICSEstablishment Name
10258086705/26/199333310Big River Zinc Corporation

Abstract: AN EMPLOYEE WAS WORKING AS A CELL ATTENDANT AT A CADMIUM ELECTROLYTIC CELL PLANT. THE EMPLOYEE WAS LIFTING CATHODES OUT OF THE 700-VOLT, DC, 17- TO 20-KILOAMPERE CELL LINE. A BUS BAR IN THE AC-SIDE OF THE AC-DC RECTIFIER SUPPLYING THE CELL LINE SHORTED TO THE BUS ENCLOSURE, CREATING A GROUND FAULT. SINCE THE BUS ENCLOSURE WAS CONNECTED TO THE FRAME OF THE BUILDING, THE GROUND FAULT IMPRESSED VOLTAGE ON METAL IN THE AREA WHERE THE EMPLOYEE WAS WORKING. THE EMPLOYEE WAS ELECTROCUTED.

Keywords: ELECTRICAL, E GI VII, ELECTROCUTED, GROUND FAULT, SYSTEM GROUNDING

Employee Details
Employee # Inspection Nr Age Sex Degree of Injury Nature of Injury Occupation
1 102580867 Fatality Electric Shock Occupation not reported

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.