Powered by GoogleTranslate

Accident Report Detail

Accident Summary Nr: 14258834 - ELECTRIC SHOCK - DIRECT CONTACT WITH ENERGIZED PARTS

Accident Summary Nr: 14258834 -- Report ID: 0317900 -- Event Date: 04/06/2000
Inspection NrDate OpenedSICNAICSEstablishment Name
30233526004/07/200036120Electric Metering Corporation

Abstract: An employee was testing a potential transformer, Model PT145, manufactured by the employer (Electric Metering Corporation). The testing procedure called for connecting several leads with alligator clips from a Falcon voltage tester to the potential transformer and then energizing the transformer with a 480-volt power supply. The employee apparently contacted a lead while it was energized and was electrocuted. The insulation on the leads was intact, and each alligator clips had rubber covering everything except the tip, which was bare metal. The employee was not using rubber insulating gloves and was standing on a concrete floor. The autopsy revealed electrical burns on the left index finger and on the middle of the palm on the right hand.

Keywords: E GI II, ELEC PROTECT EQUIP, ELECTRICAL, ELECTRICAL TESTING, ELECTROCUTED, ELEC CIRC PART--MISC

Employee Details
Employee # Inspection Nr Age Sex Degree of Injury Nature of Injury Occupation
1 302335260 Fatality Electric Shock Occupation not reported

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close