Accident Summary Nr: 118464.015 - Employee incurs shock and burns from energized bushing

Accident Summary Nr: 118464.015 -- Report ID: 0524500 -- Event Date: 07/29/2019
Inspection NrDate OpenedSICNAICSEstablishment Name
1419422.01507/31/2019221122Ameren Illinois

Abstract: At 12:45 p.m. on July 29, 2019, an employee was preparing to remove an electrical lead from a bushing on a portable substation. The employer had added a maintenance breaker which allowed maintenance personnel to supply power to a motor that moved a tap changer. The maintenance breaker allowed an extension cord, used to maintain batteries and supply power to a heater, to back-feed electricity through the transformers and up to the bushing that the employee was touching. The maintenance breaker was not operated in a manner to control the energy to the equipment. The employee incurred an electrical shock and burns to his back and hands which required hospitalization.

Keywords: Back, Circuit Breaker, Contact, Electric Shock, Electrical, Electrical Burn, Electrician, Hand, Installing, Lockout, Lockout/Tagout, Maintenance, Misjudgment, Misjudgment of Hazardous Situation, Power Plant, Power Trans Appar, Shock, Substation, Transformer

Employee Details
Employee # Inspection Nr Age Sex Degree of Injury Nature of Injury Occupation
1 1419422.015 38 M Hospitalized injury Electrical power installers and repairers

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.