Accident Summary Nr: 110278.015 - Nine employees are exposed to carbon monoxide poisoning from

Accident Summary Nr: 110278.015 -- Report ID: 0352420 -- Event Date: 09/22/2018
Inspection NrDate OpenedSICNAICSEstablishment Name
1348600.01509/24/2018238310M. B. Painting, Inc
Inspection NrDate OpenedSICNAICSEstablishment Name
1348573.01509/24/2018236220Kane Construction, Inc
Inspection NrDate OpenedSICNAICSEstablishment Name
1348591.01509/24/2018238110Richard Munday
Inspection NrDate OpenedSICNAICSEstablishment Name
1348600.01509/24/2018238310M. B. Painting, Inc

Abstract: At 7:55 a.m. on September 22, 2018, nine employees were working in a commercial building to install plumbing and drywall. Employee #1 was performing supervisory duties, Employee #2 was operating a propane powered saw (EDCO 552025P) to cut the concrete floor in preparation to install plumbing and Employees #3-9 were installing drywall. Employee #2 operated the saw from approximately 6:00 a.m. to 6:45 a.m. and again at 7:00 a.m. to 7:45 a.m. using a loading dock door as ventilation for the room (39,875 cubic feet volume of the room) while the air conditioning system continued to recirculate air from the area. Employees #3-9 first reported symptoms of carbon monoxide (CO) exposures at 7:55 a.m. and the area was evacuated and Emergency Medical Service (EMS/911) was called at 8:08 a.m. Responding EMS provided on-site treatment and transported seven of the nine employees to local hospitals for further treatment. While on-scene (approximately 8:14 a.m.), EMS measured the CO concentration in the room at approximately 200 ppm. Two other employees transported themselves, after initially refusing transport, to a local hospital for treatment. All employees received treatment for CO exposure at the hospital and released the same day.

Keywords: Air Conditioner, Carbon Monoxide, Cutting, Drywall, Installing, Operating, Propane, Saw, Ventilation, Venting
Accident Details
End Use Project Type Project Cost Stories Non-building Height Fatality
Commercial building Alteration or rehabilitation   4

Employee Details
Employee # Inspection Nr Age Sex Degree of Injury Nature of Injury Construction
1 1348600.015 35 M Hospitalized injury Distance of Fall: feet
Worker Height Above Ground/Floor: feet
Cause: Cutting concrete pavement
Fatality Cause:
2 1348600.015 23 M Hospitalized injury Distance of Fall: feet
Worker Height Above Ground/Floor: feet
Cause: Cutting concrete pavement
Fatality Cause:
3 1348573.015 51 M Hospitalized injury Distance of Fall: feet
Worker Height Above Ground/Floor: feet
Cause: Cutting concrete pavement
Fatality Cause:
4 1348591.015 51 M Non Hospitalized injury Distance of Fall: feet
Worker Height Above Ground/Floor: feet
Cause: Cutting concrete pavement
Fatality Cause:
5 1348600.015 32 M Hospitalized injury Distance of Fall: feet
Worker Height Above Ground/Floor: feet
Cause: Cutting concrete pavement
Fatality Cause:
6 1348600.015 21 M Hospitalized injury Distance of Fall: feet
Worker Height Above Ground/Floor: feet
Cause: Cutting concrete pavement
Fatality Cause:
7 1348600.015 32 M Hospitalized injury Distance of Fall: feet
Worker Height Above Ground/Floor: feet
Cause: Cutting concrete pavement
Fatality Cause:
8 1348600.015 38 M Non Hospitalized injury Distance of Fall: feet
Worker Height Above Ground/Floor: feet
Cause: Cutting concrete pavement
Fatality Cause:
9 1348600.015 41 M Hospitalized injury Distance of Fall: feet
Worker Height Above Ground/Floor: feet
Cause: Cutting concrete pavement
Fatality Cause:

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.