Powered by GoogleTranslate

Accident Report Detail

Accident Summary Nr: 10792.015 - Employee is electrocuted while installing transformer to var

Accident Summary Nr: 10792.015 -- Report ID: 0521700 -- Event Date: 03/15/2012
Inspection NrDate OpenedSICNAICSEstablishment Name
281477.01503/15/2012238210K & E Electric Inc

Abstract: At 2:00 a.m. on March 15, 2012, an employee and a coworker were retrofitting the HVAC system with a new variable air volume (VAV) control box with electrical controls. The employee accessed the air unit that was located above a drop down ceiling. The employee was working alone on the 25th floor of the building atop of a frame ladder. While installing VAV boxes to the HVAC unit, the employee followed the protocol in place in which the local electrical interrupter (switch) located on the HVAC unit was used to de-energize the unit. The switch shut off power to the unit, however, there was a 277 volt line coming into the switch. The employee contacted the live electrical parts and was electrocuted. He fell from his ladder onto the ground of the 25th floor. At 2:05 a.m., the coworker returned to the 25th floor to find the employee lying on the floor next to the ladder and unresponsive. The coworker called the emergency medical services and the employee was transported to a local hospital. The employee was killed by an electric shock.

Keywords: Electric Shock, Electrical, Electrical Box, Electrician, Electrocuted
Accident Details
End Use Project Type Project Cost Stories Non-building Height Fatality
Commercial building Alteration or rehabilitation   40 X

Employee Details
Employee # Inspection Nr Age Sex Degree of Injury Nature of Injury Occupation Construction
1 281477.015 47 M Fatality Electricians Distance of Fall: feet
Worker Height Above Ground/Floor: feet
Cause: Installing equipment (HVAC and other)
Fatality Cause:

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.