Powered by GoogleTranslate

Inspection Detail

Inspection: 309445625 - Campbell Soup Supply Company Llc

Inspection Information - Office: Toledo Area Office

 

Inspection Nr: 309445625
Report ID: 0524700
Date Opened: 03/19/2007

Site Address:
Campbell Soup Supply Company Llc
12772 E. Maumee Ave.
Napoleon, OH 43545

Mailing Address:
Maumee Ave. P.O. Box 311, Napoleon, OH 43545

Union Status: Union

SIC:2033

NAICS: 311421/Fruit and Vegetable Canning


Inspection Type: Referral

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 03/19/2007

Emphasis:

Case Closed: 05/18/2007


Related Activity
Type Activity Nr Safety Health
Referral 202099362 Yes
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 2 2
Current Violations 1 1
Initial Penalty $7,125 $0 $0 $0 $0 $7,125
Current Penalty $3,000 $0 $0 $0 $0 $3,000
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citation Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19100132 A 04/17/2007 05/04/2007 $3,000 $2,125 $0 I - Informal Settlement  
2. 01002 Serious 19100147 D04 I 04/17/2007 04/25/2007 $5,000 $5,000 $0 I - Informal Settlement Citation has been deleted.

Investigation Summary

Investigation Nr: 202088126
Event: 03/11/2007
Employee Is Burned by Pressurized Hot Water Release

At approximately 5:00 a.m. on March 11, 2007, Employee #1 was cleaning the magnet and screen on the AB line in the beverage department, which is a routine task performed at least once per shift. The company's procedure called for the isolation of two butterfly valves in the sterilization unit to block the area of the piping that contained the magnet and screen, and the opening of a drain valve to relieve the liquid under pressure in the system. After starting the valve isolation process, Employee #1 was called away to perform another task. When Employee #1 returned, he attempted to remove the clamp on the screen, for removal and cleaning. The employer's written magnet and screen cleaning procedure did not require the employee to utilize lockout-tag out during the procedure. Employee #1 had not completely isolated the system, nor confirmed that the piping was under zero pressure. The piping contained hot water (approximately 210 degrees Fahrenheit) used to sterilize the system. When Employee #1 loosened the clamp on the screen filter, the hot water, under pressure was released from the system. Employee #1 sustained second-degree thermal burns on his chest, abdomen and thighs and was hospitalized.

Keywords: BURN, HEAT, PRESSURE VESSEL, LOCKOUT, PRESSURE PIPING, PRESSURE RELEASE, HOT WATER, INATTENTION

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 309445625 Hospitalized injury Burn/Scald(Heat) Production coordinators
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.