Powered by GoogleTranslate

Inspection Detail

Inspection: 102253770 - Vernon Lofties Electrical & Refrigeration

Inspection Information - Office: Oklahoma City Area Office

 

Inspection Nr: 102253770
Report ID: 0627700
Date Opened: 09/26/1989

Site Address:
Vernon Lofties Electrical & Refrigeration
8810 N. Harrison
Shawnee, OK 74801

Mailing Address:
Route 5, Box 408, Shawnee, OK 74801

Union Status: NonUnion

SIC:1731

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 09/26/1989

Planning Guide: Safety-Construction

Emphasis:

Case Closed: 10/30/1989


Related Activity
Type Activity Nr Safety Health
Accident 360444418

Investigation Summary

Investigation Nr: 772483
Event: 09/25/1989
ELECTRIC SHOCK - CONTACT WITH ENERGIZED PARTS THRU HAND TOOL

AN ELECTRICAL CONTRACTOR WAS INSTALLING A 480-VOLT, 10-HORSEPOWER AIR COMPRESSOR IN AN EQUIPMENT ROOM IN A GLASS TEMPERING PLANT. THERE WERE THREE CONTRACTOR EMPLOYEES ON SITE (INCLUDING THE CONTRACTOR HIMSELF), BUT THE CONTRACTOR WAS THE ONLY ELECTRICIAN. THE CONTRACTOR MADE ARRANGEMENTS WITH THE PLANT EQUIPMENT OPERATOR TO DEENERGIZE THE ELECTRICAL POWER SO THAT THE AIR COMPRESSOR COULD BE INSTALLED. THE CONTRACTOR HAD RUN CONDUIT, INSTALLED A PANELBOARD AND AN ELECTRICAL BOX FOR THE DISCONNECTING MEANS, AND PULLED AND CONNECTED ALL WIRING. THE CONTRACTOR NOTIFIED THE PLANT OPERATOR THAT HE WAS GOING TO DEENERGIZE THE POWER SO THAT HE COULD CONNECT THE COMPRESSOR. ON RETURNING TO THE EQUIPMENT ROOM TO CONNECT THE COMPRESSOR WIRING TO A 480-VOLT PANELBOARD, THE CONTRACTOR NEGLECTED TO OPERATE THE DISCONNECTING MEANS TO DEENERGIZE THE CIRCUIT. WHEN THE CONTRACTOR PLACED AN ALLEN WRENCH INTO THE PANELBOARD, HE WAS ELECTROCUTED.

Keywords: E GI IV, ELECTRICAL, ELECTRICIAN, ELECTROCUTED, PANELBOARD, ELECTRICAL WORK, LOCKOUT, ELEC CIRC PART--MISC, HAND TOOL

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 102253770 Fatality Electric Shock Chief exec's & gen'l administrators, public admin.
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.