- Part Number:1926
- Part Number Title:Safety and Health Regulations for Construction
- Subpart:1926 Subpart CC
- Subpart Title:Cranes and Derricks in Construction
- Standard Number:
- Title:Power line safety (over 350 kV).
- GPO Source:
The requirements of § 1926.1407 and § 1926.1408 apply to power lines over 350 kV except:
1926.1409(a)
For power lines at or below 1000 kV, wherever the distance \"20 feet\" is specified, the distance "50 feet" must be substituted; and
1926.1409(b)
For power lines over 1000 kV, the minimum clearance distance must be established by the utility owner/operator or registered professional engineer who is a qualified person with respect to electrical power transmission and distribution.
[75 FR 48144, August 9, 2010]
[75 FR 48144, August 9, 2010]