Powered by GoogleTranslate

Alert: Due to routine maintenance on the OSHA website, some pages are temporarily unavailable.
To file a complaint with OSHA or to ask a safety and health question, call 1-800-321-6742 (OSHA).

Standard Interpretations - Table of Contents
• Standard Number: 1926.1400; 1926.1404; 1926.1412; 1926.1427; 1926.1429



March 13, 2012

Ms. Kira Henschel
Secretary, Power Crane and Shovel Association
Crane Technical Committee
6737 West Washington Street, Suite 2400
Milwaukee, WI 53214-5647

Dear Ms. Henschel:

Thank you for your September 19, 2011 letter to the Occupational Safety and Health Administration (OSHA) Directorate of Construction, as well as prior correspondence with Michael Buchet of my staff. You have asked specific questions concerning the scope of the Cranes and Derricks in Construction standard, and the certification and qualification requirements for mechanics, inspectors, and testers under this standard. This letter constitutes OSHA's interpretation of only the requirements discussed and may not be applicable to any question not delineated in your original correspondence. For clarity, we have paraphrased your questions as follows:

Question #1: Are assembly/disassembly, inspection and testing of cranes/derricks considered construction activities? What if these activities are performed in a general industry setting?

Response #1: Once a crane/derrick or its components are used in construction activities, this use—including assembly/disassembly, inspection and testing of the crane/derrick—is regulated by the Cranes and Derricks in Construction standard. Section 1926.1400 establishes the scope of the standard as follows: "This standard applies to power-operated equipment, when used in construction, that can hoist, lower and horizontally move a suspended load..." [emphasis added]. Employers using cranes or derricks to perform non-construction activities are not covered by the Cranes and Derricks in Construction standard.

In general, when an employee performs activities covered by the Cranes and Derricks in Construction standard at a construction worksite, such as assembly/disassembly, inspection, hoisting loads, or traveling from place to place on the worksite, the performance of these activities is considered construction. As a result, the employer must comply with the requirements of this standard, as well as any other applicable construction standards, because the activity in question occurs on a construction site and is expediting work that is integral to the construction process.

OSHA has provided general guidance for distinguishing between construction and general industry work in our November 18, 2003 letter to Mr. Raymond V. Knobbs, our May 11, 1999 letter to Mr. J. Nigel Ellis, our February 1, 1999 letter to Mr. Randall Tindell, and our August 11, 1994 memorandum for Regional Administrators. The OSHA website, www.osha.gov, provides access to these and other materials that aid in determining when Agency construction standards under 29 CFR 1926 apply and when they do not.

Question #2: Do the operator qualification and certification requirements under §1926.1427 apply to mechanics, inspectors or testers during assembly and disassembly under §1926.1404 and during inspection under §1926.1412?

Response #2: Not generally. When the operator certification requirement of 29 CFR 1926.1427 becomes effective on November 10, 2014, an employee who operates a crane on a construction site must meet the requirements of §1926.1427 when the employee performs activities covered by the Cranes and Derricks in Construction standard, such as assembly/disassembly, hoisting loads, or traveling from place to place on the worksite. However, the §1926.1427 operator qualification and certification requirements do not apply to maintenance, inspection or verification of crane/derrick performance by maintenance, inspection and repair personnel. Operation of a crane/derrick for maintenance, inspection or performance verification purposes must meet the requirements of §1926.1429, Qualifications of maintenance and repair employees. Personnel who have satisfied the requirements for qualification/certification under §1926.1427 may perform maintenance, inspection and verification of crane/derrick performance, provided that they also meet the requirements of §1926.1429.

Section 1926.1429 provides:

(a) Maintenance, inspection and repair personnel are permitted to operate the equipment only where all of the following requirements are met:
     (1) The operation is limited to those functions necessary to perform maintenance, inspect the equipment, or verify its performance.
    (2) The personnel either:
          (i) Operate the equipment under the direct supervision of an operator who meets the requirements of §1926.1427 ... ; or
          (ii) Are familiar with the operation, limitations, characteristics and hazards associated with the type of equipment.
(b) Maintenance and repair personnel must meet the definition of a qualified person1 with respect to the equipment and maintenance/repair tasks performed.

Question #3: May an employer rely on ASME B 30.5-2004 or -2007 requirements under 5-3.1.1 in determining what qualification requirements must be met by testers, inspectors and mechanics in order to comply with OSHA's construction crane/derrick standards?

Response #3: No. OSHA has not incorporated by reference ASME Standard B 30.6-2004 or 2007 at 5-3.1.1 in 29 CFR 1926. Although requirements under the ASME standard, including the requirement that maintenance and inspection personnel limit operation of equipment to necessary functions, may be similar to those under §1926.1429, OSHA is required to enforce §1926.1429.

Thank you for your interest in occupational safety and health. We hope you find this information helpful. OSHA requirements are set by statute, standards, and regulations. Our interpretation letters explain these requirements and how they apply to particular circumstances, but they cannot create additional employer obligations. This letter constitutes OSHA's interpretation of the requirements discussed. Note that our enforcement guidance may be affected by changes to OSHA rules. Also, from time to time we update our guidance in response to new information. To keep apprised of such developments, you can consult OSHA's website at http://www.osha.gov. If you have any further questions, please feel free to contact the Directorate of Construction at (202) 693-2020.

Sincerely,



James G. Maddux, Director
Directorate of Construction


1  A qualified person is defined under §1926.1401 as "a person who, by possession of a recognized degree, certificate, or professional standing, or who by extensive knowledge, training and experience, successfully demonstrated the ability to solve/resolve problems relating to the subject matter, the work, or the project."   [Return to Text]




Standard Interpretations - Table of Contents

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close