Powered by Google logoTranslate
Standard Interpretations - Table of Contents
• Standard Number: 1926.500

April 10, 1986

John Olivieri, President
Brama-Weber, Inc.
J.F. Sharpe Association
1015 Saw Mill River Road
Building 6B
Yonkers, New York 10710

Dear Mr. Olivieri:

This is in response to your letter of April 7, 1986, concerning your requesting a clarification of our standard railing requirements.

29 CFR 1926.500(f)(1)(vi) provides the specification criteria for a standard railing exception as follows:

(vi) Other types, sizes, and arrangements of railing construction are acceptable, provided they meet the following conditions:

(a) A smooth-surfaced top rail at a height above floor, platform, runway, or ramp level of approximately 42 inches;

(b) A strength to withstand at least the minimum requirements of 200 pounds top rail pressure with a minimum of deflection;

(c) Protection between top rail and floor, platform, runway, ramp, or stair treads, equivalent at least to that afforded by a standard intermediate rail;

(d) Eliminations of overhang of rail ends unless such overhang does not constitute a hazard.

Your proposal to install a 1/4 inch standed steel cable for the top and intermediate rails appears to meet the intent of our railing requirements. However, the wire ropes shall be secured to each support and taut at all times. In addition the maximum deflection of the top rail when a load of 200 pounds is applied in any direction at any point on the top rail shall not exceed 3 inches in one direction.

The vertical barrier (toeboard) at floor level erected along exposed edges of a floor opening must be installed to prevent falls of materials on employees working below the floor.

If we can be of further assistance, please let us know.


John B. Miles, Jr., Director
Directorate of Field Operations

Standard Interpretations - Table of Contents

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.