Violation Detail
Standard Cited: 19100157 C01 Portable fire extinguishers.
Inspection Nr: 999915.015
Citation: 01011
Citation Type: Serious
Abatement Date: 04/17/2015 2
Initial Penalty: $5,400.00
Current Penalty: $3,240.00
Issuance Date: 04/07/2015
Nr Instances: 7
Nr Exposed: 9
Related Event Code (REC):
Gravity: 5
Report ID: 0524200
Contest Date: 05/08/2015
Final Order: 08/31/2015
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | F: Formal Settlement | 08/31/2015 | $3,240.00 | 04/17/2015 | Serious | |
Penalty | C: Contested | 05/15/2015 | $5,400.00 | 04/17/2015 | Serious | |
Penalty | Z: Issued | 04/07/2015 | $5,400.00 | 04/17/2015 | Serious |
Text For Citation: 01 Item/Group: 011 Hazard:
29 CFR 1910.157(c)(1): Portable fire extinguishers were not mounted, located and identified so that they were readily accessible without subjecting the employees to injuries: a) Machine Shop, Northwest Passageway - Adjacent to the paint booth area, the fire extinguisher next to the refrigerator was blocked by boxes. b) Paint Booth, Northwest Passageway - The fire extinguisher was blocked by a table with an open container of a flammable liquid, xylene. c) Machine Shop, Southeast Passageway - The fire extinguisher mounted 78 inches above the floor, made it difficult to reach and was not readily accessible. d) Machine Shop, ASME Welding Area - The fire extinguisher was blocked by a welding helmet, Lincoln arc welding equipment, hoses, an oxygen cylinder, a box of wood blocks, rags, and nylon slings. e) Lathes Department, Northwest Exit - The fire extinguisher was mounted on the wall approximately 7 feet from the floor and was not readily accessible. f) Lathes Department, Welding Area - The fire extinguisher was mounted on a column approximately 7 feet from the floor and was blocked by a metal canopy. g) Century Department - The fire extinguisher was mounted on a steel column and was blocked by multiple nylon slings.