Violation Detail
Standard Cited: 19100107 C06 Spray finishing using flammable and combustible materials.
Inspection Nr: 996386.015
Citation: 01005A
Citation Type: Other
Abatement Date: 03/11/2015 2
Initial Penalty: $4,000.00
Current Penalty: $2,960.00
Issuance Date: 03/03/2015
Nr Instances: 1
Nr Exposed: 1
Related Event Code (REC):
Gravity:
Report ID: 0215800
Contest Date: 03/20/2015
Final Order: 03/31/2016
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | J: ALJ Decision | 03/31/2016 | $2,960.00 | 03/11/2015 | Other | |
Penalty | C: Contested | 03/25/2015 | $4,000.00 | 03/11/2015 | Serious | |
Penalty | Z: Issued | 03/03/2015 | $4,000.00 | 03/11/2015 | Serious |
Text For Citation: 01 Item/Group: 005A Hazard:
29 CFR 1910.107(c)(6): Electrical wiring and equipment outside of but within 20 feet of spraying area(s), and not separated therefrom by partitions, did not conform to the provisions for Class I, Division 2, hazardous locations: a) R&D Machine Lab; Spray Paint Booth, on or about 10/2/14: Electrical wiring and equipment including but not limited to: portable lamp; Masterflex Controller; and non-approved wiring and outlets located outside but within 20 feet of the spray booth and did not conform to the provisions for Class I, Division 2 hazardous locations.