Violation Detail
Standard Cited: 19100305 B02 I Wiring methods, components, and equipment for general use.
Inspection Nr: 985781.015
Citation: 01007C
Citation Type: Serious
Abatement Date: 11/03/2014 4
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 10/24/2014
Nr Instances: 1
Nr Exposed: 2
Related Event Code (REC):
Gravity: 5
Report ID: 0111500
Contest Date:
Final Order: 11/10/2014
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 11/10/2014 | $0.00 | 11/03/2014 | Serious | |
Penalty | Z: Issued | 10/24/2014 | $0.00 | 11/03/2014 | Serious |
Text For Citation: 01 Item/Group: 007C Hazard:
29 CFR 1910.305(b)(2)(i): All pull boxes, junction boxes, and fittings shall be provided with covers identified for the purpose. If metal covers are used, they shall be grounded. In completed installations, each outlet box shall have a cover, faceplate, or fixture canopy. Covers of outlet boxes having holes through which flexible cord pendants pass shall be provided with bushings designed for the purpose or shall have smooth, well-rounded surfaces on which the cords may bear. Main Building: The following electrical boxes were missing covers: 1. The duplex outlet below the main circuit breaker panel, energizing the alarm system. 2. The four-square box housing with two (2) on/off light switches.