Violation Detail
Standard Cited: 19100253 B04 III Oxygen-fuel gas welding and cutting.
Inspection Nr: 984296.015
Citation: 01002
Citation Type: Other
Abatement Date: 3
Initial Penalty: $3,000.00
Current Penalty: $500.00
Issuance Date: 10/28/2014
Nr Instances: 1
Nr Exposed: 15
Related Event Code (REC):
Gravity:
Report ID: 0316700
Contest Date:
Final Order: 11/20/2014
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 11/20/2014 | $500.00 | Other | ||
Penalty | Z: Issued | 10/28/2014 | $3,000.00 | Serious |
Text For Citation: 01 Item/Group: 002 Hazard:
29 CFR 1910.253(b)(4)(iii): Oxygen cylinders in storage were not separated from fuel gas cylinders or combustible materials (especially oil or grease), a minimum distance of 20 feet (6.1 m) or by a noncombustible barrier at least 5 feet (1.5 m) high having a fire resistant rating of at lest one-half hour: a) Building 3 - Oxygen tanks were observed stored less than 20 feet from LPG containers, on or about August 28, 2014. No abatement certification or documentation required.