Violation Detail
Standard Cited: 19100119 D03 I D Process safety management of highly hazardous chemicals.
Inspection Nr: 982831.015
Citation: 01001
Citation Type: Serious
Abatement Date: 3
Initial Penalty: $4,250.00
Current Penalty: $4,250.00
Issuance Date: 08/18/2014
Nr Instances: 1
Nr Exposed: 6
Related Event Code (REC):
Gravity: 5
Report ID: 0418600
Contest Date:
Final Order: 09/11/2014
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | Z: Issued | 08/18/2014 | $4,250.00 | Serious |
Text For Citation: 01 Item/Group: 001 Hazard:
29 CFR 1910.119(d)(3)(i)(D): Information pertaining to the equipment in the process did not include relief system design and design basis: a) Mobile Bay Gas Plant: On June 24, 2014 and at times prior to employees were exposed to fire and explosion hazard when operating the Stabilizer feed separator on skid PK-0804 due to the employer not having the relief design basis for PSV 1036 on Piping and instrumentation drawing MOB-8-P-010A which is set at 260 psig.