Violation Detail
Standard Cited: 19260404 B01 II Wiring design and protection.
Inspection Nr: 979943.015
Citation: 01002A
Citation Type: Serious
Abatement Date: 08/01/2014 2
Initial Penalty: $1,600.00
Current Penalty: $800.00
Issuance Date: 07/22/2014
Nr Instances: 1
Nr Exposed: 1
Related Event Code (REC):
Gravity: 5
Report ID: 0215800
Contest Date: 10/27/2014
Final Order: 03/16/2015
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | J: ALJ Decision | 03/16/2015 | $800.00 | 08/01/2014 | Serious | |
Penalty | C: Contested | 12/15/2014 | $1,600.00 | 08/01/2014 | Serious | |
Penalty | Z: Issued | 07/22/2014 | $1,600.00 | 08/01/2014 | Serious |
Text For Citation: 01 Item/Group: 002A Hazard:
29 CFR 1926.404(b)(1)(ii): On a construction site, where an assured equipment grounding program was not utilized, all 120-volt, single-phase, 15 and 20 ampere receptacle outlets which were not a part of the permanent wiring of the building or structure and which are in use by employees did not have approved ground fault circuit interrupters for personal protection: On or about 6/3/2014, At the job site: Employees were utilizing a blue extension cord to power a Milwaukee drill, battery charger and a welding machine. There was no ground fault circuit interrupter in use nor an assured equipment grounding program. Abatement certification is required for this item.