Violation Detail
Standard Cited: 19260404 B01 II Wiring design and protection.
Inspection Nr: 936079.015
Citation: 01002A
Citation Type: Serious
Abatement Date: 3
Initial Penalty: $2,000.00
Current Penalty: $2,000.00
Issuance Date: 09/23/2013
Nr Instances: 4
Nr Exposed: 4
Related Event Code (REC):
Gravity: 5
Report ID: 0134000
Contest Date:
Final Order: 11/06/2013
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 11/06/2013 | $2,000.00 | Serious | ||
Penalty | Z: Issued | 09/23/2013 | $2,000.00 | Serious |
Text For Citation: 01 Item/Group: 002A Hazard:
29 CFR 1926.404(b)(1)(ii): On a construction site, where an assured equipment grounding program was not utilized, all 120-volt, single-phase, 15 and 20 ampere receptacle outlets which were not a part of the permanent wiring of the building or structure and which are in use by employees did not have approved ground fault circuit interrupters (GFCI)for personal protection. Jobsite on roof, ground and garage: On or about August 16, 2013 employees were exposed to electrical shock hazards while using power tools and damage/frayed extension and power cords that were not GFCI protected.