Violation Detail
Standard Cited: 19100307 C Hazardous (classified) locations.
This violation item has been deleted.
Inspection Nr: 907116.015
Citation: 01002
Citation Type: Serious
Abatement Date: 07/30/2013
Initial Penalty: $5,000.00
Current Penalty: $0.00
Issuance Date: 07/18/2013
Nr Instances: 1
Nr Exposed: 6
Related Event Code (REC):
Gravity: 5
Report ID: 0316400
Contest Date: 08/12/2013
Final Order: 11/29/2013
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | F: Formal Settlement | 11/29/2013 | $0.00 | 07/30/2013 | Serious | |
Penalty | C: Contested | 08/20/2013 | $5,000.00 | 07/30/2013 | Serious | |
Penalty | Z: Issued | 07/18/2013 | $5,000.00 | 07/30/2013 | Serious |
Text For Citation: 01 Item/Group: 002 Hazard:
29 CFR 1910.307(c): Equipment, wiring methods, and installations of equipment in hazardous (classified) locations were not intrinsically safe, approved for the hazardous (classified) location, or safe for the hazardous (classified) location: (a) NW Corner of property: A 208/230 volt Carrier Liquid Chiller that was not designed for a Class 1 Division 2 location was located eight and a half feet away from an open storage bunker where several dozen cylinders of flammable acetylene gas are emptied into the immediate area as determined on May 13, 2013. (b) NW Corner of property: A 120 volt Cooper Dusk Till Dawn light that was not designed for a Class 1 Division 2 location was mounted within fifteen feet of an open storage bunker where several dozen cylinders of flammable acetylene gas are emptied into the immediate area as determined on May 13, 2013. ABATEMENT CERTIFICATION REQUIRED.