Violation Detail
Standard Cited: 19100305 E01 Wiring methods, components, and equipment for general use.
Inspection Nr: 894342.015
Citation: 01005
Citation Type: Serious
Abatement Date: 3
Initial Penalty: $5,000.00
Current Penalty: $3,000.00
Issuance Date: 07/18/2013
Nr Instances: 1
Nr Exposed: 1
Related Event Code (REC): C
Gravity: 5
Report ID: 0522500
Contest Date:
Final Order: 08/09/2013
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 08/09/2013 | $3,000.00 | Serious | ||
Penalty | Z: Issued | 07/18/2013 | $5,000.00 | Serious |
Text For Citation: 01 Item/Group: 005 Hazard:
29 CFR 1910.305(e)(1): Cabinets, cutout boxes, fittings, boxes, and panelboard enclosures. Cabinets, cutout boxes, fittings, boxes, and panelboard enclosures in damp or wet locations shall be installed so as to prevent moisture or water from entering and accumulating within the enclosures and shall be mounted so there is at least 6.35-mm (0.25-in.) airspace between the enclosure and the wall or other supporting surface. However, nonmetallic enclosures may be installed without the airspace on a concrete, masonry, tile, or similar surface. The enclosures shall be weatherproof in wet locations. a. At the workplace in the Tower Control Room, an employee was exposed to a 480 panelboard enclosure that was not suitable for damp or wet locations. The ceiling above the enclosure had multiple holes in the roof allowing rain to drain into the enclosure.