Violation Detail
Standard Cited: 19100119 D03 I B Process safety management of highly hazardous chemicals.
Inspection Nr: 470719.015
Citation: 01002
Citation Type: Serious
Abatement Date: 01/07/2013 2
Initial Penalty: $3,000.00
Current Penalty: $3,000.00
Issuance Date: 12/10/2012
Nr Instances: 2
Nr Exposed: 30
Related Event Code (REC):
Gravity: 1
Report ID: 0636900
Contest Date: 12/31/2012
Final Order: 07/08/2013
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | F: Formal Settlement | 07/08/2013 | $3,000.00 | 01/07/2013 | Serious | |
Penalty | C: Contested | 01/08/2013 | $3,000.00 | 01/07/2013 | Serious | |
Penalty | Z: Issued | 12/10/2012 | $3,000.00 | 01/07/2013 | Serious |
Text For Citation: 01 Item/Group: 002 Hazard:
29 CFR 1910.119(d)(3)(i)(B): The employer's piping and instrument diagrams (P&ID's) were not accurate and did not represent equipment that was existing and was part of the process. On or about June 14, 2012 and at times prior thereto, the employer did not ensure that the P&ID's were current and up to date, including but not limited to: a) In the isopropyl alcohol unloading port, a y-strainer filter on or about April 22, 2007, was not identified on the P&ID, IPA drawing # 0401. b) In the isopropyl alcohol feed filter area, a dp indicator, installed on on or about December 12, 2006 was not indiacted on the P&ID, IPA Drawing # 0401.