Violation Detail
Standard Cited: 19100304 G05 Wiring design and protection.
Inspection Nr: 470118.015
Citation: 01003
Citation Type: Serious
Abatement Date: 3
Initial Penalty: $2,975.00
Current Penalty: $2,975.00
Issuance Date: 07/19/2012
Nr Instances: 1
Nr Exposed: 2
Related Event Code (REC):
Gravity: 5
Report ID: 0112000
Contest Date:
Final Order: 08/13/2012
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | Z: Issued | 07/19/2012 | $2,975.00 | Serious |
Text For Citation: 01 Item/Group: 003 Hazard:
29 CFR 1910.304(g)(5): The path to ground from circuits, equipment, and enclosures was not permanent, continuous, and effective: Dietary: Continuity could not be found between the machine frame of the Hobart Model A-200 mixer and the ground prong on the plug. The grounding conductor provided in the power cord was found to be loose at the connection to the machine frame.