Violation Detail
Standard Cited: 19100027 D01 IV Scaffolds and rope descent systems.
Inspection Nr: 438832.015
Citation: 02001
Citation Type: Other
Abatement Date: 11/14/2012 2
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 11/07/2012
Nr Instances: 1
Nr Exposed: 19
Related Event Code (REC):
Gravity:
Report ID: 0627510
Contest Date: 11/29/2012
Final Order: 04/21/2014
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | J: ALJ Decision | 04/21/2014 | $0.00 | 11/14/2012 | Other | |
Penalty | C: Contested | 11/30/2012 | $0.00 | 11/14/2012 | Other | |
Penalty | Z: Issued | 11/07/2012 | $0.00 | 11/14/2012 | Other |
Text For Citation: 02 Item/Group: 001 Hazard:
1910.27(d)(1)(iv): Cage(s) did not extend down the ladder to a point not less than 7 feet nor more than 8 feet above the base of the ladder: On or about June 1, 2012, and at times prior thereto, the #2 Vacuum Heater Tower Ladder equipped with a cage that did not extend down to a point not less than 7 feet nor more than 8 feet above the base of the ladder. The bottom of the cage ended approximately 9-feet, 5-inches above the base of the ladder.