Violation Detail
Standard Cited: 19100119 E03 IV Process safety management of highly hazardous chemicals.
This violation item has been deleted.
Inspection Nr: 438832.015
Citation: 01003A
Citation Type: Serious
Abatement Date: 11/28/2012 2
Initial Penalty: $5,500.00
Current Penalty: $0.00
Issuance Date: 11/07/2012
Nr Instances: 1
Nr Exposed: 30
Related Event Code (REC):
Gravity: 5
Report ID: 0627510
Contest Date: 11/29/2012
Final Order: 04/21/2014
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | J: ALJ Decision | 04/21/2014 | $0.00 | 11/28/2012 | Serious | |
Penalty | C: Contested | 11/30/2012 | $5,500.00 | 11/28/2012 | Serious | |
Penalty | Z: Issued | 11/07/2012 | $5,500.00 | 11/28/2012 | Serious |
Text For Citation: 01 Item/Group: 003A Hazard:
29 CFR 1910.119(e)(3)(iv): The process hazard analysis did not address the consequences of failure of engineering and administrative controls: On or about June 1, 2012, and at times prior thereto, the employer did not address the consequences of closing an intervening valve on a line upstream of a relief device when it conducted the PHA for the Alky/PDA Unit and did not consider the block valve in the vent line of the Low Pressure Condensate Pot in the Alky/PDA Unit.