Violation Detail
Standard Cited: 19100119 J04 II Process safety management of highly hazardous chemicals.
Inspection Nr: 313026163
Citation: 01012
Citation Type: Serious
Abatement Date: 01/19/2010 X
Initial Penalty: $5,000.00
Current Penalty: $3,500.00
Issuance Date: 12/29/2009
Nr Instances: 1
Nr Exposed: 125
Related Event Code (REC):
Gravity: 10
Report ID: 0625700
Contest Date:
Final Order:
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 01/21/2010 | $3,500.00 | 01/19/2010 | Serious | |
Penalty | Z: Issued | 12/29/2009 | $5,000.00 | 01/19/2010 | Serious |
Text For Citation: 01 Item/Group: 012 Hazard: REFINERY
29 CFR 1910.119(j)(4)(ii): Inspections and testing procedures performed on process equipment to maintain its mechanical integrity, did not follow recognized and generally accepted good engineering practices: This violation was observed on or about August 27, 2009, where the employer failed to calculate corrosion rates and/or determine thickness measurements in the Hydrocracker Unit for piping circuits HC-V-002 (effluent piping), HC-V- 014 (effluent), HC-V-022 (kerosene and diesel effluent). This condition exposed employees to fire and explosion hazards. Pursuant to 29 CFR 1903.19(d), within 10 calendar days of the date of the citation, the employer must submit documentation showing that it is in compliance with the standard, including describing the steps it is taking to ensure that all required piping thickness measurements have been completed to calculate corrosion rates.