Violation Detail
Standard Cited: 19100119 D03 III Process safety management of highly hazardous chemicals.
Inspection Nr: 311611081
Citation: 02031A
Citation Type: Serious
Abatement Date: 04/19/2010 X
Initial Penalty: $70,000.00
Current Penalty: $7,000.00
Issuance Date: 03/08/2010
Nr Instances: 5
Nr Exposed: 40
Related Event Code (REC):
Gravity: 10
Report ID: 0524700
Contest Date: 03/31/2010
Final Order: 09/27/2018
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | R: Review Commission | 09/27/2018 | $7,000.00 | Serious | ||
Penalty | Z: Issued | 03/08/2010 | $70,000.00 | Willful |
Text For Citation: 02 Item/Group: 031A Hazard: REFINERY
29 CFR 1910.119(d)(3)(iii): For existing equipment designed and constucted in ac cordance with codes, standards, or practices that are no longer in general use, the employer does not determine and document that the equipment in the process i s designed, maintained, inspected, tested, and operated in a safe manner: BP-Hus ky Refining, LLC - Oregon, Ohio: The employer permits the existence of permanent connections between the plant fire water system and process systems, that can l ead to the contamination of fire water supply with hydrocarbons or other process fluids, in that, a. In the Isocracker 2 Unit, there is a cross connection at th e 6" supply water to the cooler box on the east side of the unit; b. In the Hydr ogen Unit there are two cross connection instances on the blowdown drum; c. In t he Sulfur Recovery Unit, there are two filter backwash cross connections; d. In the Reformer 2 regeneration system, there is a cross connection between th e quench and cooling water; e. There are cross connections on the discharge side s of the fire water booster pumps in the FCC Unit. Pursuant to 29 CFR 1903.19, w ithin ten (10) calendar days of the abatement date, the employer must submit doc umentation that it has abated the hazard. In addition, under 29 CFR 1903.19(e), the employer, must submit an abatement plan describing the actions it is taking to ensure that it is in compliance with the standards for fire safety in accorda nce with recognized and generally accepted good engineering practices, such as N FPA 30 and API 2001. The abatement plan shall establish dates during the next th ree months to determine when the cross connections will be eliminated. Once the plan has been fully implemented, the employer must submit certification of its full compliance with the standard.e