Violation Detail
Standard Cited: 19100303 G01 I B General.
Inspection Nr: 1490660.015
Citation: 01004A
Citation Type: Serious
Abatement Date: 10/27/2020 2
Initial Penalty: $5,783.00
Current Penalty: $4,000.00
Issuance Date: 10/19/2020
Nr Instances: 2
Nr Exposed: 25
Related Event Code (REC):
Gravity: 1
Report ID: 0418600
Contest Date:
Final Order: 10/30/2020
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 10/30/2020 | $4,000.00 | 10/27/2020 | Serious | |
Penalty | Z: Issued | 10/19/2020 | $5,783.00 | 10/27/2020 | Serious |
Text For Citation: 01 Item/Group: 004A Hazard:
29 CFR 1910.303(g)(1)(i)(B): For electric equipment operating at 600 volts, nominal, or less to ground, and likely to require examination, adjustment, servicing, or maintenance while energized, the width of the working space in front of electrical equipment was less than the width of the equipment or 762 mm (30 inches), whichever was greater: a) Warehouse Area (Northwest Electrical Panel): On or about August 28, 2020, and times prior, the employer failed to keep clear an unobstructed path of at least 762 mm (30 inches) in front of Panelboard No. EF-176809; exposing employees to hazards such as but not limited to slip or trip hazards during emergency events. b) Warehouse Area (Southwest Electrical Panel): On or about August 28, 2020, and times prior, the employer failed to keep clear an unobstructed path of at least 762 mm (30 inches) in front of Panelboard No. BS-510580; exposing employees to hazards such as but not limited to slip or trip hazards during emergency events.