Violation Detail
Standard Cited: 19100106 B02 IV F 1 Flammable liquids.
This violation item has been deleted.
Inspection Nr: 1430156.015
Citation: 01002
Citation Type: Serious
Abatement Date: 03/11/2020
Initial Penalty: $12,145.00
Current Penalty: $0.00
Issuance Date: 02/13/2020
Nr Instances: 1
Nr Exposed: 6
Related Event Code (REC): A
Gravity: 10
Report ID: 0626300
Contest Date: 03/13/2020
Final Order: 08/28/2020
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | F: Formal Settlement | 08/28/2020 | $0.00 | 03/11/2020 | Serious | |
Penalty | C: Contested | 04/03/2020 | $12,145.00 | 03/11/2020 | Serious | |
Penalty | Z: Issued | 02/13/2020 | $12,145.00 | 03/11/2020 | Serious |
Text For Citation: 01 Item/Group: 002 Hazard:
29 CFR 1910.106(b)(2)(iv)(f)(1): Tanks and pressure vessels storing Category 1 flammable liquids were not equipped with venting devices which are normally closed except when venting to pressure or vacuum conditions. Tanks and pressure vessels storing Category 2 flammable liquids and Category 3 flammable liquids with a flashpoint below 100 °F (37.8 °C) were not equipped with venting devices which are normally closed except when venting under pressure or vacuum conditions, or with approved flame arresters: (a) On or about September 6, 2019, at the site employees were exposed to burn hazards when an open temporary storage tank (recirculation tank) was being used to circulate the well.