Violation Detail
Standard Cited: 19100305 E01 Wiring methods, components, and equipment for general use.
Inspection Nr: 1412820.015
Citation: 01005B
Citation Type: Serious
Abatement Date: 10/08/2019 2
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 09/26/2019
Nr Instances: 1
Nr Exposed: 20
Related Event Code (REC): C
Gravity: 5
Report ID: 0111500
Contest Date:
Final Order: 10/16/2019
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 10/16/2019 | $0.00 | 10/08/2019 | Serious | |
Penalty | Z: Issued | 09/26/2019 | $0.00 | 10/08/2019 | Serious |
Text For Citation: 01 Item/Group: 005B Hazard:
29 CFR 1910.305(e)(1): Cabinets, cutout boxes, fittings, boxes, and panelboard enclosures. Cabinets, cutout boxes, fittings, boxes, and panelboard enclosures in damp or wet locations were not installed so as to prevent moisture or water from entering and accumulating within the enclosures and were not mounted so there is at least 6.35-mm (0.25-in.) airspace between the enclosure and the wall or other supporting surface. However, nonmetallic enclosures may be installed without the airspace on a concrete, masonry, tile, or similar surface. The enclosures shall be weatherproof in wet locations. Main Electrical Room: The main breaker panel and the high voltage circuit panel were installed in wet location and were not installed to protect the equipment from damage.