Violation Detail
Standard Cited: 19100119 D02 I D Process safety management of highly hazardous chemicals.
This violation item has been deleted.
Inspection Nr: 1392221.015
Citation: 01001A
Citation Type: Serious
Abatement Date: 10/18/2019
Initial Penalty: $10,419.00
Current Penalty: $0.00
Issuance Date: 09/25/2019
Nr Instances: 5
Nr Exposed: 10
Related Event Code (REC):
Gravity: 5
Report ID: 0213900
Contest Date: 10/28/2019
Final Order: 04/07/2021
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | F: Formal Settlement | 04/07/2021 | $0.00 | 10/18/2019 | Serious | |
Penalty | C: Contested | 10/28/2019 | $10,419.00 | 10/18/2019 | Serious | |
Penalty | Z: Issued | 09/25/2019 | $10,419.00 | 10/18/2019 | Serious |
Text For Citation: 01 Item/Group: 001A Hazard:
29 CFR 1910.119(d)(2)(i)(D): Information concerning the technology of the process did not include safe upper and lower limits for such items as temperatures, pressures, flows or compositions: a) Ammonia refrigeration system: The employer did not maintain information pertaining to the technology of the process, including, but not limited to the operating pressures and temperatures for intercooler IC-500, to ensure that the minimum design metal temperature was not exceeded, on or about 4/10/19. b) Ammonia refrigeration system: The employer did not maintain information pertaining to the technology of the process, including, but not limited to the operating pressures and temperatures for thermosyphon receiver TS-700, to ensure that the minimum design metal temperature was not exceeded on or about 4/10/19. c) Ammonia refrigeration system: The employer did not maintain information pertaining to the technology of the process, including, but not limited to the operating pressures and temperatures for the high pressure receiver HPR-600, to ensure that the minimum design metal temperature was not exceeded on or about 4/10/19. d) Ammonia refrigeration system: The employer did not maintain information pertaining to the technology of the process, including, but not limited to the operating pressures for surge drums LVS 1-4 servicing the spiral coil freezer, to ensure that the minimum design metal temperature was not exceeded, on or about 4/10/19. e) Ammonia refrigeration system: The employer did not maintain information pertaining to the technology of the process, including, but not limited to the operating pressures and temperatures for the pump package recirculator PPR-400, to ensure that the minimum design metal temperature was not exceeded, on or about 4/10/19. NOTE: IN ADDITION TO ABATEMENT CERTIFICATION, THE EMPLOYER IS REQUIRED TO SUBMIT ABATEMENT DOCUMENTATION FOR THIS ITEM. FAILURE TO COMPLY WILL RESULT IN AN ADDITIONAL PENALTY OF $1000.00 IN ACCORDANCE WITH 29 CFR 1903.19.