Violation Detail
Standard Cited: 19100305 B01 II Wiring methods, components, and equipment for general use.
Inspection Nr: 1373448.015
Citation: 01011A
Citation Type: Serious
Abatement Date: 1
Initial Penalty: $4,508.00
Current Penalty: $3,155.60
Issuance Date: 04/23/2019
Nr Instances: 4
Nr Exposed: 10
Related Event Code (REC):
Gravity: 5
Report ID: 0112000
Contest Date:
Final Order: 06/02/2019
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 06/02/2019 | $3,155.60 | Serious | ||
Penalty | Z: Issued | 04/23/2019 | $4,508.00 | Serious |
Text For Citation: 01 Item/Group: 011A Hazard:
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed: A. Receiving Dock: On, or about, January 24, 2019, an opening was left in the dead front panel of Panel P2, a Siemens panelboard. B. Bread Oven, Start End: On, or about, January 24, 2019, a knockout was left open on the top of a duplex receptable box mounted on the right side of the oven enclosure. C. Roll Oven, Finish End: On, or about, January 24, 2019, an opening in the dead front of Panel RU2, a General Electric panelboard, was covered with duct tape. D. Maintenance Shop: On, or about, April 5, 2019, two openings were left in the dead front of the Cutler-Hammer panelboard.