Violation Detail
Standard Cited: 19100304 B04 II B Wiring design and protection.
Inspection Nr: 1373448.015
Citation: 01009B
Citation Type: Serious
Abatement Date: 1
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 04/23/2019
Nr Instances: 1
Nr Exposed: 4
Related Event Code (REC):
Gravity: 1
Report ID: 0112000
Contest Date:
Final Order: 06/02/2019
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 06/02/2019 | $0.00 | Serious | ||
Penalty | Z: Issued | 04/23/2019 | $0.00 | Serious |
Text For Citation: 01 Item/Group: 009B Hazard:
29 CFR 1910.304(b)(4)(ii)(B): Where connected to a branch circuit supplying two or more receptacles or outlets, a receptacle supplied a total cord-and plug-connected load in excess of the maximum specified in Table S-4: Maintenance Shop: On, or about, January 31, 2019, a 15 ampere relocatable power tap was used to energize a microwave oven, toaster oven and coffee maker. The maximum load permitted on the power tap was 12 amperes. The rating for each of the three appliances exceeded the 12 ampere limit.