Violation Detail
Standard Cited: 19100304 B04 Wiring design and protection.
Inspection Nr: 1373448.015
Citation: 01009A
Citation Type: Serious
Abatement Date: 1
Initial Penalty: $3,381.00
Current Penalty: $2,366.70
Issuance Date: 04/23/2019
Nr Instances: 2
Nr Exposed: 63
Related Event Code (REC):
Gravity: 1
Report ID: 0112000
Contest Date:
Final Order: 06/02/2019
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 06/02/2019 | $2,366.70 | Serious | ||
Penalty | Z: Issued | 04/23/2019 | $3,381.00 | Serious |
Text For Citation: 01 Item/Group: 009A Hazard:
29 CFR 1910.304(b)(4): Outlet devices had an ampere rating less than the load being served: A. Breakroom: On, or about, January 24, 2019, two microwave ovens were energized through the same 15 ampere wall receptacle. The combined load of the two microwave ovens was 25.8 amperes. B. Maintenance Shop: On, or about, January 31, 2019, a microwave oven, toaster oven and coffee maker were energized through the same 20 ampere wall receptacle. The combined load of any two of the appliances exceeded the rating of the receptacle.