Violation Detail
Standard Cited: 19100303 G01 I A General.
Inspection Nr: 1373448.015
Citation: 01008A
Citation Type: Serious
Abatement Date: 06/10/2019 2
Initial Penalty: $5,304.00
Current Penalty: $3,712.80
Issuance Date: 04/23/2019
Nr Instances: 2
Nr Exposed: 4
Related Event Code (REC):
Gravity: 5
Report ID: 0112000
Contest Date:
Final Order: 06/02/2019
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 06/02/2019 | $3,712.80 | 06/10/2019 | Serious | |
Penalty | Z: Issued | 04/23/2019 | $5,304.00 | 06/10/2019 | Serious |
Text For Citation: 01 Item/Group: 008A Hazard:
29 CFR 1910.303(g)(1)(i)(A): For electric equipment operating at 600 volts, nominal, or less to ground, and likely to require examination, adjustment, servicing, or maintenance while energized, the depth of the working space in the direction of access to live parts (as measured from the live parts where they were exposed or from the enclosure front or opening where they were enclosed) was less than indicated in Table S-1 of Subpart S of Part 1910: Roll Conveyor, Finish End: Metal railings that were installed in front of the Depanner and Conveyor control enclosures limited the working space in front of the equipment to less than the required distance required by Table S-1 which was 42 inches.