Violation Detail
Standard Cited: 19100305 A01 I Wiring methods, components, and equipment for general use.
This violation item has been deleted.
Inspection Nr: 1364908.015
Citation: 01006
Citation Type: Serious
Abatement Date: 06/28/2019
Initial Penalty: $8,525.00
Current Penalty: $0.00
Issuance Date: 06/06/2019
Nr Instances: 1
Nr Exposed: 3
Related Event Code (REC):
Gravity: 5
Report ID: 0729700
Contest Date:
Final Order: 06/28/2019
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 06/28/2019 | $0.00 | 06/28/2019 | Serious | |
Penalty | Z: Issued | 06/06/2019 | $8,525.00 | 06/28/2019 | Serious |
Text For Citation: 01 Item/Group: 006 Hazard:
29 CFR 1910.305(a)(1)(i): Metal raceways, cable armor, and other metal enclosures for conductors were not connected to all boxes, fittings, and cabinets to provide effective electrical continuity: Employees were exposed to fire, explosion and electrical shock hazards. Employees engaged in housekeeping and grain handling activities in the elevator main floor (gallery area) by the man-lift were exposed to fire, explosion and electrical shock hazards in that the electrical metal conduit was not completely connected or closed to provide effective electrical continuity and to avoid accumulation of dust coming inside for the integrity of the entire system of the elevator. 29 CFR 1903.19(c)(1) requires certification that the abatement of the above violation is complete.