Violation Detail
Standard Cited: 19100106 D04 IV Flammable liquids.
Inspection Nr: 1364763.015
Citation: 01004
Citation Type: Serious
Abatement Date: 05/20/2019 2
Initial Penalty: $6,819.00
Current Penalty: $3,000.00
Issuance Date: 04/03/2019
Nr Instances: 2
Nr Exposed: 4
Related Event Code (REC):
Gravity: 5
Report ID: 0111700
Contest Date: 04/24/2019
Final Order: 04/27/2022
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | F: Formal Settlement | 04/27/2022 | $3,000.00 | 05/20/2019 | Serious | |
Penalty | C: Contested | 05/14/2019 | $6,819.00 | 05/20/2019 | Serious | |
Penalty | Z: Issued | 04/03/2019 | $6,819.00 | 05/20/2019 | Serious |
Text For Citation: 01 Item/Group: 004 Hazard:
29 CFR 1910.106(d)(4)(iv): Ventilation. Every inside storage room was not provided with either a gravity or a mechanical exhaust ventilation system. Such system was not designed to provide for a complete change of air within the room at least six times per hour. Location: flammable storage rooms On or about December 6, 2018, the closed container flammable storage room had no ventilation system to ensure at least six air changes per hour.